Parker 591 governor maintenance
Publish:Shenzhen City Jia Hong Wei Technology Co., Ltd. Time:2021-10-05
Parker 591 governor maintenance
Model: Parker 590P governor
Fault cause: power on operation missing pulse alarm
Fault analysis: the customer Parker 591 governor is used for steel plate shearing and feeding. According to the customer‘s fault prompt, an alarm occurs during startup. The fault is that the six pulse armature current waveform loses a pulse. When the motor load exceeds 1.5 times the discontinuous point value, the alarm will be started. Most of the fault causes are harmonic interference, trigger board fault, loose plug and damaged thyristor. After measuring and eliminating peripheral faults, it is found that the output waveform is obviously asymmetric during operation. Measure the drive circuit and eliminate the problem of the main board. The thyristor is normal after measurement. It is found that the drive IC is damaged during power on online measurement. After replacement, the load test fault is removed.
Possible causes of Parker 591 governor alarm
Accts failed current transformer fault not connected to current transformer
Autotune abort auto tuning failure auto tuning extension is not flexible
Autotune error auto tuning operation error
Aux power fail auxiliary power failure
Checksum fail (EEPROM) checksum failed
The enable config configuration selects a valid state
Encoder failed encoder signal failure
Encoder alarm
Field fail excitation fault excitation current too low
Field over 1 excitation overcurrent motor excitation overcurrent
Health word normal word
Health store normal storage
Heatsink trip radiator overheat trip radiator fin overheat
Ia FBK cal fail armature current self test failed
Ia Inst cal fail armature current self test failed
Language checksum fail language mode selection error
Missing pulse missing armature current pulse
Over I trip motor armature overcurrent
Over speed
Over volts motor armature overvoltage
Phase lock PLL AC synchronization failed
Lack of preparation for pre peady fault
P3 state P3 port status warning
Speed FBK alarm
Stall trip locked rotor tripping Motor Locked Rotor timeout tripping
Thermistor motor overheating
Trip reset
3-phase failed 3-phase fault no 3-phase power supply
JiaHongWei maintains common faults of Parker 591 governor and European EUROTHERM DC governor, such as no display, overcurrent, overvoltage, undervoltage, overheating, grounding, parameter error, alarm, thyristor breakdown, no excitation, jitter, etc. maintenance scope of European DC governor:
Is3 series, ssd590 series, ssd591 series, ssd590 + series, ssd590c, ssd590p, ssd512c, ssd514c series JiaHongWei professional maintenance of the following DC governor brands:
Siemens, Lenz, Continental,, abb, Fuji, Mitsubishi, Toshiba, bagra, Yaskawa, AB, Hitachi, Sanken, Emerson, Danfoss, Delta, Taian, Samsung, LG, Migao, Panasonic, Viking, truzler, Dr. Rexroth, baumiller, etc